SLC TWIN PRO2 A
On-line double-conversion UPS 1000 VA to 3000 VA
Advanced on-line protection for sensitive and critical loads
Backup shorter than normal

Solution: Connect device to mains for 12 hours to fully charge batteries. If problem persists, replace batteries or consult distributor.

No indication or audible alarm when equipment connected to mains

Solution: Check mains supply and input cable connection.

Code: 43

Possible cause: The UPS turns off automatically due to overload at output.

Solution: Disconnect the excess loads from the output sockets and restart it.

Code: bLOW

Issue: Low battery.

Solution: Disconnect loads as UPS will shortly leave output without power. When mains supply returns, batteries will charge automatically.

Code: EP

Possible cause: EPO (emergency power off) function activated.

Solution: Close EPO signal circuit (fit connector with jumper) to deactivate it.

Code: l4

Possible cause: UPS turns off automatically due to short circuit at output.

Solution: Check output wiring and that connected loads not short-circuited.

Code: NC

Possible cause: Internal or external batteries badly connected.

Solution: Check all batteries properly connected.

Code: SF

Possible cause: Neutral to earth fault detection. Phase and neutral input cables inverted.

Solution: Disconnect input plug from AC power socket and invert connection of phase and supply neutral (rotate plug 180º).

Code: TP

Possible cause: The temperature of the UPS is very high or the fan is locked or does not work.

Solution: Check the fans and contact the distributor or seller or, failing that, our TSS.

Barcelona Web Design: MontawebMONTAWEB.com
Welcome to Salicru. Select country/language
Argentina   Español
Bolivia   Español
Brazil   Português
Canada   Français   English
Caribbean Islands   English
Chile   Español
Colombia   Español
Costa Rica   Español
Cuba   Español
Dominican Republic   Español
Ecuador   Español
El Salvador   Español
Guatemala   Español
Mexico   Español
Nicaragua   Español
Panama   Español
Paraguay   Español
Peru   Español
United States   English
Uruguay   Español
Venezuela   Español
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it, adapt the content to your tastes and personalise our advertising, marketing and social media posts. Click on the corresponding buttons to accept all of them, reject them or configure your settings. Please see our Cookie Policy for more information.