RE3 M 15-2
RE3 M 15-2
Electronic voltage stabilisers single-phase from 15 kVA
The fastest and the most accurate electronic regulation system of the market
Regulation margin:
±15% (2)
Output voltage (V):
220 V, 230 V, 240 V
System power (VA/W):
15000 / 15000
Transformador separador (>40dB):
-
Code: 6A3AA000004
EAN: 8436035926015
Specifications
Technical specifications
INPUT / OUTPUT
Input / Output
Monofásico
INPUT
Voltage
220 V, 230 V, 240 V
Regulation range
±15% (2)
Rated frequency
50 / 60 Hz
Frequency range
47.5 ÷ 63 Hz
OUTPUT
Voltage
220 V, 230 V, 240 V
Accuracy
Better than ± 2%
Power (VA/W)
15000 / 15000
Total harmonic distortion (THDv)
Nil
Frequency
48 ÷ 63 Hz
Response time
<100 ms
Performance
> 97%
Admissible overloads
200% for 1 minute
Current
65,2
BYPASS
Type
Static
GENERAL
Ambient temperature
-10º C ÷ + 45º C
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2428 m.a.s.l.
Degree of protection
IP20
Cooling
Natural or forced depending on power rate
Acoustic noise at 1 metre
< 45 dB(A)(3)
Mean time between failures (MTBF)
60,000 hours
Mean time to repair (MTTR)
58 minutes
Electrical noise attenuation on common mode
With ultra-isolation transformer > 120 dB
STANDARDS
Safety
UNE EN IEC 61558-2-12; UNE EN IEC 61558-2-13
Electromagnetic compatibility (EMC)
UNE EN IEC 62041
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
590
Width (mm)
340
Height (mm)
580
WEIGHT
Weight (kg)
69
(1) Ask for other setting
(2) Other ranges under request
(3) <65 dB(A) for models with forced ventilation
View distributor
Select Region and Country/Province to view Distributors
Accessories
Communications
NIMBUS ROUTER 4G
Device that uses 4G mobile networks to provide Internet connection via WiFi or Ethernet.
Code: 663AA002241
EAN: 8436584876281
NIMBUS SNMP Card
Nimbus Ethernet adapter / SNMP web adapter. Connection to the Salicru cloud (IoT - MQTT). Modbus TCP and RS232 protocol. SNMP V2. Shutdown of servers, via RCCMD software.
Code: 663AA002223
EAN: 8436584876274
Generic
BE-RE3 M 15-2/2
External Manual Bypass for 15 kVA single-phase RE3 series equipment allows maintenance to be carried out without interrupting the power supply to the protected equipment.
Code: 6A4OP000011
Downloads
Documents
Data sheet
Catalogues
Manuals
Certificates & Declarations
Instructions
Request information about RE3 M 15-2
Welcome to Salicru. Select country/language
Australia English
Bangladesh English
Camboya English
China English
India English
Indonesia English
Japan English
Kazakhstan English
Laos English
Malaysia English
Myanmar English
New Zealand English
Pakistan English
Philippines English
Singapore English
South Korea English
Sri Lanka English
Taiwan English
Thailand English
Vietnam English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.















MONTAWEB.com