SLC-30-CUBE3+ PS 62AB360
SLC-30-CUBE3+ PS 62AB360
Uninterruptible Power Systems three-phase from 30 kVA Peak Shaving
Energy efficiency and reduced consumption peaks
Input voltage (V):
3 x 380 / 3 x 400 / 3 x 415 V (3F + N)
Output voltage (V):
3 x 380 / 3 x 400 / 3 x 415 V (3F + N)
Power (VA):
30000
Type:
UPS Standard
Code: 681RB000003
Specifications
Technical specifications
TECHNOLOGY
On-line, double conversion, HF, DSP control
INPUT
Voltage
3 x 380 / 3 x 400 / 3 x 415 V (3F + N)
Voltage range
+15% / -20% (configurable)
Rated frequency
50 / 60 Hz
Total harmonic distortion (THDi)
100% load: <1.5% / 50% load: <2.5% / 10% load: <6.0%
Power factor
1 from 10% load
Rectifier topology
Three-phase IGBT full wave, soft start, PFC, transformerless
Input limit for peak shaving
Adjustable between 10%-100% of the power required for the output load
OUTPUT
Power factor
0,9(2)
Voltage
3 x 380 / 3 x 400 / 3 x 415 V (3F + N)
Dynamic accuracy
± 2% dynamic
Static accuracy
± 1% steady
Response time accuracy
20 ms for load steps 0% ÷ 100% and voltage drop up to -5%
Power (VA/W)
30000 / 27000
Total harmonic distortion (THDv) Linerar load
<0.5%
Total harmonic distortion (THDv) Non~linear load
<1.5% (EN-62040-3)
Synchronised frequency
50/60 Hz ±5 Hz (selectable)
Frequency
50/60 Hz +/- 5 Hz (selectable)
Frequency accuracy (battery mode)
50/60 Hz ±0.05%
Synchronous speed
From 1 Hz/s to 10 Hz/s (programmable)
Total performance in On-line mode
7.5÷60 kVA: 92.0%÷93.0% / 80÷200 kVA: 94.0%÷95.0%
Admissible overloads
125% for 10 min / 150% for 60 s / >150% for 20ms
Crest factor
3,2 a 1
MANUAL BYPASS
Protections
No breaks
STATIC BYPASS
Type and activation criteria
Solid state, controlled by microprocessor
Transfer times in On-line
Nil
Transfer to bypass
Immediate, for overloads exceeding 150%
Retransfer
Automatic, after alarm deactivation
Peak Shaving
User configurable activation
BATTERY
Battery type
Lead acid, sealed, maintenance free
Charging voltage regulation
Batt-Watch
Peak shaving function
Sizing for energy storage and supplying the load’s peaks in demand
COMMUNICATION
Ports
1 x RS232/RS485 + 1xUSB,with Modbus protocol
Relay interface
4 x AC failure, bypass, low battery and general
Intelligent slot
1, for SNMP
Monitoring software
Viewpower / UPSMAN
Backlit LCD display
LCD display, LEDs and keyboard
GENERAL
Operating temperature
0º C ÷ +40º C
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2.400 m.s.n.m. (3)
Acoustic noise at 1 metre
<52 dB(A)(4)
IMPLEMENTATIONS
Nº Cabinets (Ups + BAT)
1 + 0
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN-62040-2
Operation
VFI-SS-11 (EN-62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
770
Width (mm)
450
Height (mm)
1100
WEIGHT
Weight (kg)
378
(1) Up to 100 kVA.
(2) Only for three-phase input/output models. PF=0.8 for all other configurations.
(3) Power degradation for higher altitudes up to a maximum of 5,000 masl.
(4) <65 dB(A) for 80 to 120 kVA models / <70 dB(A) for 160 to 200 kVA models.
View distributor
Select Region and Country/Province to view Distributors
Downloads
Documents
Data sheet
Catalogues
General Catalogue
Manuals
Certificates & Declarations
Instructions
Software
VIEWPOWER HTML
Windows
installViewPower_Windows - 109MB Download
Software questions about SLC-30-CUBE3+ PS 62AB360?
Request information about SLC-30-CUBE3+ PS 62AB360
Welcome to Salicru. Select country/language
Algeria Français
Angola Português
Bahrain English
Congo Français
Côte d'Ivoire Français
Egypt English
Iraq English
Jordan English
Kenya English
Kuwait English
Lebanon English
Libya English
Madagascar Français
Mali Français
Mauritania Français
Morocco Français
Niger Français
Nigeria English
Oman English
Qatar English
Reunion Français
Saudi Arabia English
Senegal Français
South Africa English
Syria English
Tanzania Français
Turkey English
Uganda English
United Arab Emirates English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.
We’ve detected that you're accessing from United States. Would you like to see the website for your country?











MONTAWEB.com