SLC-#/8 ADAPT2 112 A
SLC-#/8 ADAPT2 112 A
Modular three-phase Uninterruptible Power Systems of up to 112000 VA
Flexibility, availability and reliability in superior electrical protection
Module power (VA / W):
14000 / 14000
Input voltage (V):
3x 208 / 220 V (3F + N)
Output voltage (V):
3x 208 / 220 V (3F + N)
System power (VA/W):
112000 / 112000
Code: 694RA100249
Specifications
Technical specifications
TECHNOLOGY
On-line double-conversion, Three-level PWM, DSP control
PHYSICAL
Module/System
Sistema
No. Modules (#)
1 to 8
INPUT
Voltage
3x 208 / 220 V (3F + N)
Voltage range
-40% +15% (1)
Rated frequency
50 / 60 Hz
Frequency range
40 - 70 Hz
Total harmonic distortion (THDi)
≤4%
Power factor
>0.99
OUTPUT
Power factor
1
Voltage
3x 208 / 220 V (3F + N)
Dynamic accuracy
±1,5%
Static accuracy
±1%
Power (VA/W)
112000 / 112000
Maximum power (VA/W)
112000 / 112000
Frequency
50 / 60 Hz
Module performance (On-line)
>96%
Performance in Smart Eco-mode
98%
Admissible overloads
<125% for 10 min / <150% for 1 min
Admissible overloads
<110% for 1 hour / <125% for 10 min / <150% for 1 min / >150% for 200 ms
Crest factor
3:1
MANUAL BYPASS
Protections
Uninterrupted
STATIC BYPASS
Type
Static thyristor
Three-phase voltage (V)
3 x 200 / 208 (3P + N)
Admissible overloads
≤110% constant / ≤130% for 1 hour / ≤150% for 1 minute / >150% for 5 seconds
BATTERY
Battery type
Pb-Ca, VRLA, lead acid, gel, Ni-Cd, Li-Ion
Charging voltage regulation
Batt-watch
Charger maximum power (W)
20% de la potencia total del sistema
COMMUNICATION
Display
7” touchscreen and LEDs
Ports
RS-232, RS-485, relays and USB
Intelligent slot
1 x Nimbus SNMP/1 x Nimbus extended relays
GENERAL
Operating temperature
0º C ÷ +55º C (2)
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2,400 masl(3)
Acoustic noise at 1 metre
<56 dB(A)
SYSTEMS
Maximum no. modules per system
2 or 3
STANDARDS
Safety
EN IEC 62040-1
Electromagnetic compatibility (EMC)
EN IEC 62040-2
Operation
VFI-SS-11 (EN 62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
916
Width (mm)
482
Height (mm)
1550
WEIGHT
Weight (kg)
178
(1) Linear % load derating: For 14 kVA from -20% to -27% and for 30 kVA from -20% to -40%.
(2) Power derating for higher altitudes up to +40ºC.
(3) Power degradation for higher altitudes, up to a maximum of 5,000 masl.
Video
View distributor
Select Region and Country/Province to view Distributors
Downloads
Documents
Data sheet
Catalogues
General Catalogue
Manuals
Certificates & Declarations
Instructions
Request information about SLC-#/8 ADAPT2 112 A
Welcome to Salicru. Select country/language
Australia English
Bangladesh English
Camboya English
China English
India English
Indonesia English
Japan English
Kazakhstan English
Laos English
Malaysia English
Myanmar English
New Zealand English
Pakistan English
Philippines English
Singapore English
South Korea English
Sri Lanka English
Taiwan English
Thailand English
Vietnam English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.















MONTAWEB.com