TECHNOLOGY
On-line, double conversion, HF, DSP control
INPUT
Voltage
3x380 / 3x400 / 3x415 V
Voltage range
+15% / -20% (configurable)
Rated frequency
50 / 60 Hz
Total harmonic distortion (THDi)
100% load: <1.5% / 50% load: <2.5% / 10% load: <6.0%
Power factor
1 from 10% load
Rectifier topology
Three-phase IGBT full wave, soft start, PFC, transformerless
OUTPUT
Power factor
0.9
Voltage
3 x 208 / 3 x 220 / 3 x 380 / 3 x 400 / 3 x 415 V (3F + N)
Dynamic accuracy
± 2% dynamic
Static accuracy
± 1% steady
Response time accuracy
20 ms for load steps 0% ÷ 100% and voltage drop up to -5%
Power (VA/W)
15000 / 13500
Total harmonic distortion (THDv) Linerar load
<0.5%
Total harmonic distortion (THDv) Non~linear load
<1.5% (EN-62040-3)
Frequency
50/60 Hz ±0.05%
Eco-mode performance
95,5%
Total performance in On-line mode
7.5÷60 kVA: 92.0%÷93.0% / 80÷200 kVA: 94.0%÷95.0%
Admissible overloads
125% for 10 min / 150% for 60 s / >150% for 20ms
Crest factor
3,4 a 1
COMMUNICATION
Ports
1 x RS232/RS485 + 1xUSB,with Modbus protocol
Relay interface
4 x AC failure, bypass, low battery and general
Intelligent slot
1, for SNMP
Monitoring software
For Windows, Linux and Mac
GENERAL
Operating temperature
0º C ÷ +40º C
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2,400 masl (3)
Acoustic noise at 1 metre
52 dB(A)(2)
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN-62040-2
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
775
Width (mm)
450
Height (mm)
1100
WEIGHT
Weight (kg)
102
(1) Single-phase 120 / 127 V available up to 30 kVA inclusive and three-phase 3 x 208 / 3 x 220 V available up to 100 kVA inclusive.
(2) <65 dB(A) for 80 to 120 kVA models / <70 dB(A) for 160 and 200 kVA models.
(3) Power derating for higher altitudes up to 5000 masl.
View distributor
Select Region and Country/Province to view Distributors
Accessories
Generic
Empty Batt Mod 1x62 of 24 Ah for SLC CUBE3+
Battery cabinet without batteries prepared for installation 1 branch of 62 batteries of 24 Ah for UPS models series SLC CUBE3+.
Code: O6819999998
Empty Batt Mod 1x62 of 45 Ah for SLC CUBE3+
Battery cabinet without batteries prepared for installation 1 branch of 62 batteries of 45 Ah for UPS models series SLC CUBE3+.
Code: O6819999997
Empty Batt Mod 2x62 of 7 / 9 / 12 Ah for SLC CUBE3+
Battery cabinet without batteries prepared for the installation of 2 branches of 62 7 / 9 / 12 Ah batteries for UPS models SLC CUBE3+ series.
Code: O6819999999
Downloads
Documents
Data sheet
Catalogues
General Catalogue
Certificates & Declarations
Instructions
Request information about CF-15-CUBE3+ 60/50HZ
Welcome to Salicru. Select country/language
Australia English
Bangladesh English
Camboya English
China English
India English
Indonesia English
Japan English
Kazakhstan English
Laos English
Malaysia English
Myanmar English
New Zealand English
Pakistan English
Philippines English
Singapore English
South Korea English
Sri Lanka English
Taiwan English
Thailand English
Vietnam English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.














MONTAWEB.com