SLC-300-XTRA B1
Specifications
Technical specifications
TECHNOLOGY
On-line, double conversion, DSP control
INPUT
Voltage
3x380 / 3x400 / 3x415 V
Voltage range
+15% / -20% (@ 3 x 400 V)
Rated frequency
50 / 60 Hz (45-65 Hz)
Frequency range
±5 Hz or ±10Hz adjustable
Total harmonic distortion (THDi)
<3%
Power factor
>0.99
Protection
Internal fuses
OUTPUT
Power factor
0.9
Voltage
3x380 V / 3x400 V / 3x415 V (3F+N)
Voltage accuracy
±1 %. Steady state -unbalanced load-: ±2 %. Dynamic state -load steps 20% - 100% - 20%: ±5 %.
Ripple
1%
Total harmonic distortion (THDv) Non~linear load
<5%
Synchronised frequency
±2 % others under request
Frequency
50 / 60 Hz
Frequency accuracy (battery mode)
±0.001 Hz
Synchronous speed
1Hz/s
Eco-mode performance
>98%
Admissible overloads
125% for 10 min. / 150% for 1 min / 200% for 10 s />200% for 100ms
Admissible overloads
125% for 10 min. / 150% for 1 min
Crest factor
3 a 1
Parallel
Through protocol CANBUS
MANUAL BYPASS
Protections
Without interruption
100–300 kVA
Seriell
STATIC BYPASS
Type and activation criteria
Solid state, control by microprocessor
Voltage (V)
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph + N)
Transfer time
Nil
Transfer to bypass
Immediate for overloads of over 150%
Retransfer
Automatic after alarm disappearance
Voltage range
±10% (Selectable between 1 ÷ 20%)
Input
Independent
Frequency
50 / 60 Hz
Admissible overloads
1000% for 1 cycle
RECTIFIER
Protection
Against transitory overvoltages
BATTERY
Protection
Against overvoltages and undervoltages
Battery type
Lead acid, sealed, maintenance free(1)
Charge type
IU in accordance with DIN41773
Recharge time
4 hours, @ 80% of capacity
Charging voltage regulation
Batt-Watch
Battery test
Manual + Automatic
CHARGER
Temperature voltage compensation
2,267 V/+25º C
COMMUNICATION
Ports
RS-232, USB, Emergency Power Off (EPO), Port for monitoring battery switch
Intelligent slot
2 (One for SNMP and another one for MODBUS protocol)
Backlit LCD display
LCD + LED block diagram
INDICATIONS
Alarm
mains fault, scheduled maintenance necessary, input phase rotation not correct, common alarm, rectifier off, mbcb bus closed, rectifier failure, epo bus, wrong dc voltage, asymmetric load, batt in test, service required, bcb open, battery in diesel mode,
OTHER FUNCTIONS
Emergency stop (EPO)
Yes
GENERAL
Operating temperature
0º C ÷ +40º C
Storage temperature
-10ºC ÷ +60ºC (with batteries) / -10ºC ÷ +70ºC (without batteries)
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
< 2,400 m.s.n.m.
Degree of protection
IP20
Acoustic noise at 1 metre
< 60 dB
Mean time between failures (MTBF)
383000 hours with bypass
SYSTEMS
Maximum no. parallel systems
Yes, up to 6 units
IMPLEMENTATIONS
Nº Cabinets (Ups + BAT)
1 + 2
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN-62040-2
Operation
VFI-SS-11 (EN-62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
855
Width (mm)
1220
Height (mm)
1905
WEIGHT
Weight (kg)
1170
(1) Ni-Cd under request.
View distributor
Select Region and Country/Province to view Distributors
Accessories
Communications
AS-400 GX5 CON_R_AUX4
Relay interface for configuring inputs/outputs and switching contacts as required, up to 4 inputs/outputs.
Code: 663AA002213
EAN: 8436035929450
CS141 SENSOR CABLE
SNMP Card adapter cable for temperature and humidity sensor.
Code: 663AA002270
EAN: 8436584876298
MODEM GSM4G SMS BOX CS141-6 GX
GSM modem with an additional safety measure whereby coordinators and responsible technicians receive an SMS immediately if a fault occurs in the UPS system.
Code: 663AA002264
EAN: 8436584875406
NIMBUS ROUTER 4G
Device that uses 4G mobile networks to provide Internet connection via WiFi or Ethernet.
Code: 663AA002241
EAN: 8436584876281
NIMBUS SNMP Card
Nimbus Ethernet adapter / SNMP web adapter. Connection to the Salicru cloud (IoT - MQTT). Modbus TCP and RS232 protocol. SNMP V2. Shutdown of servers, via RCCMD software.
Code: 663AA002223
EAN: 8436584876274
RS-485 MODBUS CARD
Nimbus RS485 card with MODBUS protocol.
Code: 697OP000002
EAN: 8436035924127
SENSORMANAGER II CS141/CS121
Control unit allowing the connection of analogue and digital sensors for strategic room monitoring. 8 analogue inputs, 4 digital inputs and 4 digital outputs.
Code: 663AA002220
EAN: 8436584876267
SNMP Card GX5 CS141BSC-6
Ethernet adapter / SNMP web adapter. Modbus TCP protocol. SNMP V2 and V3. Shutdown of servers, by means of RCCMD software.
Code: 663AA002254
EAN: 8436584874270
SNMP RTH BOX GX5 CS141LM-6
Ethernet adapter / SNMP web adapter. Modbus TCP and RS485 protocol. SNMP V2 and V3. Outdoor location. Shutdown of servers, by means of RCCMD software. Connection with sensors and actuators.
Code: 663AA002260
EAN: 8436584875550
SNMP RTH CARD GX5 CS141SCM-6
Ethernet adapter / SNMP web adapter. Modbus TCP and RS485 protocol. SNMP V2 and V3. Shutdown of servers, via RCCMD software. Connection with sensors and actuators.
Code: 663AA002265
EAN: 8436584874881
SNMP TH BOX GX5 CS141-6
Ethernet adapter / SNMP web adapter. Modbus TCP and RS232 protocol. SNMP V2 and V3. Outdoor location. Shutdown of servers, via RCCMD software. Connection with sensors and actuators.
Code: 663AA002256
EAN: 8436584875536
SNMPTH CARD GX5 CS141SC-6
Ethernet adapter / SNMP web adapter. Modbus TCP and RS232 protocol. SNMP V2 and V3. Shutdown of servers, via RCCMD software. Connection with sensors and actuators.
Code: 663AA002259
EAN: 8436584875543
Software RCCMD
Application that allows the simultaneous and safe shutdown of different servers remotely. Communication via SNMP.
Code: 663AA002119
EAN: 8436584875246
SOFTWARE UNMS II-150
Network management system that can actively manage monitored UPS and external components and execute automatic actions. Up to 150 licenses.
Code: 663AA002141
EAN: 8436584876236
SOFTWARE UNMS II-200
Network management system that can actively manage monitored UPS and external components and execute automatic actions. Up to 200 licences.
Code: 663AA002261
EAN: 8436584874577
SOFTWARE UNMS II-25
Network management system that can actively manage monitored UPS and external components and execute automatic actions. Up to 25 licenses.
Code: 663AA002139
EAN: 8436584870388
SOFTWARE UNMS II-50
Network management system that can actively manage monitored UPS and external components and execute automatic actions. Up to 50 licenses.
Code: 663AA002140
EAN: 8436584876229
SOFTWARE UNMS II-9
Network management system that can actively manage monitored UPS and external components and execute automatic actions. Up to 9 licenses.
Code: 663AA002138
EAN: 8436035923212
Software UPSMAN
Application that allows simultaneous and safe shutdown of computers that are directly connected to the UPS via USB or serial network port.
Code: 663AA002123
EAN: 8436584876212
T GX Sensor
Temperature sensor (range -25º C to +100º C). Compatible SNMP Card adapter required.
Code: 663AA002129
EAN: 8436035923953
T+H GX Sensor
Temperature sensor (range -25º C to +100º C) and relative humidity (range 0% to 100%). SNMP compatible SNMP Card adapter required
Code: 663AA002128
EAN: 8436035923946
Generic
BM-XTRA-P-300-B-4/4
External Manual Bypass for SLC XTRA 300 kVA series equipment allows maintenance to be performed without interrupting the power supply to the protected equipment.
Code: 695OP000015
EAN: BM-XTRA-P-300-B-4/4
CAB SLC BZ192 DB9M/DB9H 1.8m
Communication extension cable, DB9M/DB9H connectors, 1.8m length
Code: 663AC000005
CAB SLC BZ192 DB9M/DB9H 10m
Communication extension cable, DB9M/DB9H connectors, 10 m long
Code: 663AC000006
CAB SLC BZ192 DB9M/DB9H 3m
Communication extension cable, DB9M/DB9H connectors, 3m length
Code: 663AC000004
CAB SLC BZ192 DB9M/DB9H 5m
Communications extension cable, DB9M/DB9H connectors, 5m length
Code: 663AC000003
INTERFACE A RELÉS XTRA
Potential-free contacts that allow the following information to be available remotely: general alarm, mains failure, low battery, inverter out of range, bypass,
Code: 695OP000011
PARALLEL KIT XTRA<=300KVA
For redundant and parallel installations. Suitable for installations up to 6 UPS. Parallel cable length: 20 metres. Please consult us for longer lengths.
Code: 695OP000001
Downloads
Documents
Data sheet
Catalogues
Manuals
Certificates & Declarations
Declaration of conformity SLC X-TRA
Instructions
Request information about SLC-300-XTRA B1
Welcome to Salicru. Select country/language
Australia English
Bangladesh English
Camboya English
China English
India English
Indonesia English
Japan English
Kazakhstan English
Laos English
Malaysia English
Myanmar English
New Zealand English
Pakistan English
Philippines English
Singapore English
South Korea English
Sri Lanka English
Taiwan English
Thailand English
Vietnam English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.














MONTAWEB.com