SLC TWIN RT2 LION
On-line double conversion tower/rack UPS, 1000-3000 VA, with lithium-ion batteries
Maximum protection density
Battery backup time much shorter than expected.

Possible cause: Batteries not fully charged.

Solution: Charge batteries for at least 8 hours and then check their charge level. If problem persists, contact distributor or seller or, failing that, our TSS.

 

Possible cause: Batteries defective.

Solution: Contact distributor or seller or, failing that, our TSS for battery replacement.

When connecting UPS to mains, display does not illuminate nor show any indications

Possible cause: No voltage at input.

Solution: Check for mains voltage.

 

Possible cause: Input power cables badly connected.

Solution: Check input power cables firmly connected to mains and UPS.

 

Possible cause: Input cable connected to IEC output connector on UPS.

Solution: Correctly connect input cable to respective IEC connector.

Code: O9

Possible cause: UPS overloaded:

Solution: Disconnect or shut down the excess loads connected to the UPS output.

 

Possible cause: UPS overloaded. Equipment connected to the UPS is directly powered by the mains input through the bypass.

Solution: Disconnect or shut down the excess loads connected to the UPS output.

 

Possible cause: After repeated overloads, the UPS is in Bypass mode. Equipments connected to the output are powered directly by the mains.

Solution: Disconnect or shut down the excess loads connected to the UPS output, shut down the device and restart it.

Code: 27

Possible cause: Voltage of batteries too high or charger faulty.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: 28

Possible cause: Voltage of batteries too low or charger faulty.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: 2A

Possible cause: Charger short-circuited at its output.

Solution: Check whether the connection of the external battery pack connected to the UPS is short-circuited.

Code: 49

Possible causa: Sobrecorrent d'entrada del SAI.

Solució: Desconnectar l'excés de càrregues de les preses de sortida.

Code: 4S

Possible cause: The charger does not provide output and the battery voltage is less than 10 V per element.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: NC

Possible cause: Internal or external batteries badly connected.

Solution: Check all batteries properly connected.

Code: OA

Possible cause: Fans fault.

Solution: Check the fans and contact the distributor or seller or, failing that, our TSS.

Code: OD

Possible cause: The temperature of the UPS is very high or the fan is locked or does not work.

Solution: Check the fans and contact the distributor or seller or, failing that, our TSS.

Code: OL

Possible cause: UPS overloaded.

Solution: Disconnect excess load from UPS output sockets.

 

Possible cause: The UPS is overloaded and connected loads are powered directly from the mains through the Bypass.

Solution: Disconnect excess load from UPS output sockets.

 

Possible cause: After repetitive overloads, the UPS is locked in Bypass mode and connected loads are powered directly from the mains through the Bypass.

Solution: Disconnect the excess loads from the output sockets, shut down the device and restart it.

Code: Ol

Possible cause: Internal or external batteries badly connected.

Solution: Check all batteries properly connected.

Code: SF

Possible cause: Neutral to earth fault detection. Phase and neutral input cables inverted.

Solution: Disconnect input plug from AC power socket and invert connection of phase and supply neutral (rotate plug 180º).

Code: TP

Possible cause: The temperature of the UPS is very high or the fan is locked or does not work.

Solution: Check the fans and contact the distributor or seller or, failing that, our TSS.

Codes: Ol, O2, O3, ll, l2, l3 and 4l

Possible cause: Internal fault in UPS.

One of two possible situations may occur in this state:

1. The load is still powered, but from the mains through the UPS Bypass.

2. The load is no longer powered.

Solution: Contact distributor or seller or, failing that, our TSS.

Codes: Ol, O2, O3, O4, ll, l2, l3, l4, lA, 2l, 24, 3S, 36, 4l, 42 or 43

Possible cause: Internal fault in UPS. One of two possible situations may occur in this state:

1. The load is still powered, but from the mains through the UPS Bypass.

2. The load is no longer powered.

Solution: Contact distributor or seller or, failing that, our TSS.

Barcelona Web Design: MontawebMONTAWEB.com
Welcome to Salicru. Select country/language
Argentina   Español
Bolivia   Español
Brazil   Português
Canada   Français   English
Caribbean Islands   English
Chile   Español
Colombia   Español
Costa Rica   Español
Cuba   Español
Dominican Republic   Español
Ecuador   Español
El Salvador   Español
Guatemala   Español
Mexico   Español
Nicaragua   Español
Panama   Español
Paraguay   Español
Peru   Español
United States   English
Uruguay   Español
Venezuela   Español
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it, adapt the content to your tastes and personalise our advertising, marketing and social media posts. Click on the corresponding buttons to accept all of them, reject them or configure your settings. Please see our Cookie Policy for more information.