SLC TWIN PRO2 T UL
On-line double conversion UPS 6 and 10 kVA with PF=1
Enhanced protection for mid-range systems with single-phase power supply
Backup shorter than normal

Solution: Connect device to mains for 12 hours to fully charge batteries. If problem persists, replace batteries or consult distributor.

No indication or audible alarm when equipment connected to mains

Solution: Check mains supply and input cable connection.

Code: bLOW

Issue: Low battery.

Solution: Disconnect loads as UPS will shortly leave output without power. When mains supply returns, batteries will charge automatically.

Code: bOPN
  • Possible cause: Open battery.

Solution: B1 systems with external battery module(s), verify that they are correctly connected to the UPS.

 

If the problem persists, check the battery circuit or fill out the incident management form. Access here

Systems without external battery modules: check battery circuits or fill out the incident management form. Access here

Code: bYPA

Issue: During mains outage, load not supplied through Bypass mode.

Solution: Switch on by pressing ON button down for more than one second.

Code: EP

Possible cause: EPO (emergency power off) function activated.

Solution: Close EPO signal circuit (fit connector with jumper) to deactivate it.

Code: EPO

Issue: EPO function is enabled.

Solution: Check EPO switch circuit.

Code: FANF
  • Possible cause: Fan failure.

Solution: Check the UPS ventilation (clogged grilles, fan operation). In the event of an incident need, fill in the incident management form.

 

Code: OVLD

Issue: Overload.

Solution: Check loads, remove any non-critical ones. Power requested is higher than UPS’s.

Code: STBY

Issue: Load not supplied through no output mode.

Solution: Switch on by pressing ON button down for more than one second.

Codes: HIGH / CHGF / dCHF / bUSH / bUSL / bSFT / bUSS / INVH / INVL / ISFT / NTCO
  • Possible cause: Internal failures.

Solution: Faulty UPS. Fill out the incident management form. Click here Click here

Codes: ITPH  / OVTP / TEPH
  • Possible cause: Temperature incidents.

Solution: Check UPS ventilation (clogged grilles, fan operation) and room ambient temperature. If necessary after verifications, fill out the incident management form. Click here Click here

Barcelona Web Design: MontawebMONTAWEB.com
Welcome to Salicru. Select country/language
Andorra   Català   Español
Armenia   English
Austria   Deutsch   English
Belarus   English
Belgium   Français   English
Bulgaria   English
Croatia   English
Cyprus   English
Czech Republic   English
Denmark   English
Estonia   English
Finland   English
France   Français
Georgia   English
Germany   Deutsch   English
Greece   English
Hungary   English
Ireland   English
Italy   English
Latvia   English
Lithuania   English
Luxembourg   Français   Deutsch
Malta   English
Netherlands   English
Norway   English
Poland   English
Portugal   Português
Romania   English
Russia   English
Serbia   English
Slovakia   English
Spain   Español   Català
Sweden   English
Switzerland   Français   Deutsch   English
Ukraine   English
United Kingdom   English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it, adapt the content to your tastes and personalise our advertising, marketing and social media posts. Click on the corresponding buttons to accept all of them, reject them or configure your settings. Please see our Cookie Policy for more information.