EQX2 10002-T
Specifications
Technical specifications
INPUT
Maximum DC input power (W)
16000
INPUT DC
Maximum voltage (V)
1100
Starting voltage (V)
180
Max. short-circuit current - Isc PV(A)
20/20 A
Inputs per MPPT
1/1
Inputs per MPPT
2
MPPT voltage range (VDC)
160 ÷ 1000
Input maximum current per tracker (A)
15/15(1)
MPPT performance
99,9%
OUTPUT
Power factor
0.8 inductive…0.8 capacitive
Maximum power (W)
10000
Network voltage
3x400 V Three-phase (3L, N, PE)(2)
Voltage ranges
195.5 ÷ 253 V (Ph-N) according to UNE 217002
Maximum apparent output power (VA)
11000
Max. total harmonic distortion (THD)
<3%
Frequency
50 Hz (45.5 ÷ 55 Hz) / 60 Hz (55 ÷ 65 Hz)
Rated output current (A)
14.5
Performance EU
97,9% ÷ 98,2%
Maximum performance
98,1% ÷ 98,6%
COMMUNICATION
Ports
RS485, WiFi
INDICATIONS
Type
2 LED states, OLED display
PROTECTION
Input DC disconnector
Included
Integrated in the device
Inverse polarity DC, Residual Current, DC disconnector, Over-voltage, Over-temperature, Differential, Islanding operation, AC short-circuit, Over-voltage AC
Over-voltage protection category
PV: II / AC: II
GENERAL
Contamination level
PD2/PD3
Self-consumption (at night)
<1 W
Operating temperature
-30°C ~ +60°C (de-rate for temperature >45°C)
Relative humidity
0 ~ 100%
Maxium operating altitude
3,000 masl (power degradation up to 4,000 m)
Degree of protection
IP65
Cooling
Natural convection (no fans)(3)
Acoustic noise at 1 metre
≤25 dB(3)
Terminal type
MC4
Installation
Indoor and outdoor installation / Wall support
Topology
Transformerless Non-isolated (On grid)
STANDARDS
Safety / EMC
IEC 62109-1/2 / EN 61000-6-2/3
Energy efficiency
IEC EN UNE 61683
Environmental tests
IEC EN UNE 60068-2-1/2/14/30
Operation / Protection
UNE EN 62116:2014, IEC 61727:2004, UNE 217002:2020, UNE 217001:2020
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
175
Width (mm)
550
Height (mm)
410
WEIGHT
Weight (kg)
23
(1) For PV inverters with more than 1 string per MPPT, please enquire about potential current restrictions
(2) For three-phase voltages without a neutral (triangle), ask
(3) For models from EQX2 17002-T (inclusive) Smart fan cooling and ≤ 72 dB
(4) Consult available regulations for other countries
(5) The single MPPT is distributed across the 10 inverter inputs
Video
View distributor
Select Region and Country/Province to view Distributors
Accessories
Generic
485/WIFI EQX2-T
WiFi communication module. DIN rail mounting in the AC panel. Single-phase 230 Vac power supply. Provides 24-hour data on generation, grid injection/consumption and consumption of the installation. A three-phase smart meter is required depending on the installation current.
Code: 6B2OP000018
Measurements (mm): 30x105x65
EAN: 8436584873761
ESM3T 300D50 EQX2
Three-phase smart meter (energy meter). Includes 3 current transformers of 300 A, internal diameter of 50 mm, wired (2 m)* and with connector, for current measurement.
Code: 6B2OP000016
Measurements (mm): 52x84x73
EAN: 8436584873679
ESM3T 90D24 EQX2
Three-phase smart meter (energy meter). Includes 3 current transformers of 90 A, internal diameter of 24 mm, wired (2 m)* and with connector, for current measurement.
Code: 6B2OP000017
Measurements (mm): 52x84x73
EAN: 8436584873686
LAN MODULE EQX2
LAN communication module. Direct installation to the inverter. Provides generation data via cable.
Code: 6B2OP000022
Measurements (mm): 51x116x30
EAN: 8436584874362
SLC ENERGY MANAGER T ../5
Smart energy meter from the SLC Energy Manager series by SALICRU. Three-phase model without transformers and with relay output. Advanced solution for efficient energy management in photovoltaic installations, with wired or Wi-Fi configuration and self-configuration of current transformers.
Code: 6B2OQ000036
Measurements (mm): 70x101x70
EAN: 8436584874805
Weight: 0.5
SLC ENERGY MANAGER T 300D50
Smart energy meter from the SLC Energy Manager series by SALICRU. Three-phase model with 300 A transformer and relay output. Advanced solution for efficient energy management in photovoltaic installations, with wired or Wi-Fi configuration and self-configuration of current transformers.
Code: 6B2OR000004
Measurements (mm): 70x101x70
EAN: 8436584874850
Weight: 0.5
SLC ENERGY MANAGER T 80D16
Smart energy meter from the SLC Energy Manager series by SALICRU. Three-phase model with 80 A transformer and relay output. Advanced solution for efficient energy management in photovoltaic installations, with wired or Wi-Fi configuration and self-configuration of current transformers.
Code: 6B2OR000003
Measurements (mm): 70x101x70
EAN: 8436584874843
Weight: 0.5
Downloads
Documents
Data sheet
Catalogues
Manuals
Monitored Manual 24-hour EQUINOX2 T / T-RV
Certificates & Declarations
Declaration of conformity EQUINOX2 T / T-RV
Instructions
Request information about EQX2 10002-T
Welcome to Salicru. Select country/language
Armenia English
Belarus English
Bulgaria English
Croatia English
Cyprus English
Czech Republic English
Denmark English
Estonia English
Finland English
France Français
Georgia English
Greece English
Hungary English
Ireland English
Italy English
Latvia English
Lithuania English
Malta English
Netherlands English
Norway English
Poland English
Portugal Português
Romania English
Russia English
Serbia English
Slovakia English
Sweden English
Ukraine English
United Kingdom English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.
We’ve detected that you're accessing from United States. Would you like to see the website for your country?













MONTAWEB.com