EQX 5000-2T
Specifications
Technical specifications
INPUT DC
Maximum voltage (V)
900
Max. short-circuit current - Isc PV(A)
11A x 2
Inputs per MPPT
2/1
INPUT
Maximum DC input power (W)
5500
Working-out rank (Vdc)
200-800
MPPT rank (Vdc)
260-800
Max. input current per MPPT x Number of MPPTs
10A x 2
OUTPUT
Power factor
0.9 inductive to 0.9 capacitative (adjustable)
Maximum power (W)
5000
Network voltage
Three-phase (L1, L2, L3, N, PE) o (L1, L2, L3, PE)
Voltage ranges
Three-phase 320~460 Vac
Maximum apparent output power (VA)
5000
Total harmonic distortion (THDi)
<2%
Frequency
50 Hz (47-51,5 Hz) / 60 Hz (57-61,5 Hz)
Rated output current (A)
8
Performance EU
96,28%
Maximum performance
98,04%
COMMUNICATION
Ports
Standard: RS485 / Optional: Wifi, LAN, 4G and GPRS
INDICATIONS
Type
2” back-lit LCD + status LEDs
PROTECTION
Input DC disconnector
Included
Integrated in the device
Input: Over-voltage, under-voltage and over-current, DC insulation resistance monitoring, inverse polarity, residual current detection / Output: anti-islanding, over-voltage, under-voltage, over-current and short-circuit, overtemperature, frequency out of range, high DC component in AC.
Over-voltage protection category
PV: II / AC: II
GENERAL
Contamination level
3
Self-consumption (at night)
<1W
Operating temperature
-25°C~+60°C (de-rate for temperature >45°C)
Relative humidity
0~100%
Maxium operating altitude
2000m (de-rate for altitude >2000m)
Degree of protection
IP65
Isolation
Class I
Cooling
Natural convection (no fans)
Acoustic noise at 1 metre
≤30 dB
Terminal type
MC4 or compatible
Installation
Indoor and outdoor installation / Wall support
Topology
Transformerless
STANDARDS
Certificate
RD 244/2019; UNE 206007-1 IN(1)
Safety / EMC
IEC 62109-1/2 / EN 61000-6-2/3
Energy efficiency
IEC 61683
Environmental tests
IEC 60068-2-1/2/14/30
Operation / Protection
IEC 62116
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
155
Width (mm)
360
Height (mm)
532
WEIGHT
Weight (kg)
20
(1) Consult available regulations for other countries
View distributor
Select Region and Country/Province to view Distributors
Downloads
Documents
Data sheet
Catalogues
Manuals
Certificates & Declarations
Instructions
Request information about EQX 5000-2T
Welcome to Salicru. Select country/language
Australia English
Bangladesh English
Camboya English
China English
India English
Indonesia English
Japan English
Kazakhstan English
Laos English
Malaysia English
Myanmar English
New Zealand English
Pakistan English
Philippines English
Singapore English
South Korea English
Sri Lanka English
Taiwan English
Thailand English
Vietnam English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.















MONTAWEB.com