SLC-#/9-ADAPT2 54 A
SLC-#/9-ADAPT2 54 A
Modular three-phase Uninterruptible Power Systems of up to 54000 VA
Modularity, optimisation and efficiency in electrical safety for data centres
Module power (VA / W):
9.000 / 9.000
No. Modules:
1 to 6
Input voltage (V):
3x 208 / 220 V (3F + N)
Output voltage (V):
3x 208 / 220 V (3F + N)
System power (VA/W):
54000 / 54000
Code: 694OQ000079
Specifications
Technical specifications
TECHNOLOGY
On-line double-conversion, HF, DSP control
PHYSICAL
Module/System
Sistema
No. Modules (#)
1 to 6
INPUT
Rated three-phase voltage (3P+ N + E)
3 x 208 / 220 V
Voltage range
-40% +25% (Depending on charge)(1)
Rated frequency
50 / 60 Hz
Frequency range
40 - 70 Hz
Total harmonic distortion (THDi)
≤3%
Power factor
>0.99
OUTPUT
Power factor
1
Rated three-phase voltage (3P + N + E)
3 x 208 / 220 V
Static accuracy
±1%
Power (VA/W)
54000 / 54000
Maximum power (VA/W)
54000 / 54000
Total harmonic distortion (THDv) Linerar load
<1%
Total harmonic distortion (THDv) Non~linear load
<5%
Frequency
50 / 60 Hz
Module performance (On-line)
> 96%
Performance in Smart Eco-mode
99%
Admissible overloads
<110% for 1 hour / <125% for 10 min / <150% for 1 min / >150% for 200 ms
Crest factor
3:1
MANUAL BYPASS
Protections
Uninterrupted (optional)(2)
STATIC BYPASS
Type
Static thyristor
Transfer time
0 ms
Admissible overloads
≤110% constant / ≤130% for 1 hour / ≤150% for 1 minute / >150% for 5 seconds
BATTERY
Battery type
Pb-Ca, VRLA, lead acid, gel, Ni-Cd, Li-Ion
Charging voltage regulation
Batt-watch
Charger maximum power (W)
20% of total system power
COMMUNICATION
Display
7” touchscreen, LEDs and keypad
Ports
RS-232, RS-485 and relays
Intelligent slot
1 x Nimbus SNMP/1 x Nimbus extended relays
GENERAL
Operating temperature
0º C ÷ +55º C (3)
Relative humidity
Up to 95%, non-condensing
Maxium operating altitude
2,400 masl(4)
Acoustic noise at 1 metre
<54 dB(A) (According to number of modules)
STANDARDS
Safety
EN-IEC 62040-1
Electromagnetic compatibility (EMC)
EN-IEC 62040-2
Operation
VFI-SS-11 (EN-62040-3)
Corporate cerification
ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm)
751
Width (mm)
485
Height (mm)
1033
WEIGHT
Weight (kg)
101
(1) Linear % load derating from -20% to -40%.
(2) Not included in subracks. Excellent for cabinet systems.
(3) Power derating for higher altitudes up to +40ºC.
(4) Power degradation for higher altitudes, up to a maximum of 5,000 masl.
Video
View distributor
Select Region and Country/Province to view Distributors
Downloads
Documents
Data sheet
Catalogues
Manuals
Certificates & Declarations
Instructions
Request information about SLC-#/9-ADAPT2 54 A
Welcome to Salicru. Select country/language
Argentina Español
Bolivia Español
Brazil Português
Caribbean Islands English
Chile Español
Colombia Español
Costa Rica Español
Cuba Español
Dominican Republic Español
Ecuador Español
El Salvador Español
Guatemala Español
Mexico Español
Nicaragua Español
Panama Español
Paraguay Español
Peru Español
United States English
Uruguay Español
Venezuela Español
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it,
adapt the content to your tastes and personalise our advertising, marketing and social media posts.
Click on the corresponding buttons to accept all of them, reject them or configure your settings.
Please see our Cookie Policy for more information.












MONTAWEB.com