SPS ADVANCE T (Type G)
Line-interactive sine-wave UPS tower 850 VA to 3000 VA
Reliable protection in tower format for computer rooms
When turning on UPS, LED of “On-Off” button surround flashes and sounds a beep every 30 seconds

Possible cause: No voltage at input.

Solution: Check for mains voltage.

 

ossible cause: Input power cables badly connected.

Solution: Check input power cables firmly connected to mains and UPS.

Battery backup time much shorter than expected.

Possible cause: Batteries not fully charged.

Solution: Charge batteries for at least 8 hours and then check their charge level. If problem persists, contact distributor or seller or, failing that, our TSS.

 

Possible cause: Batteries defective.

Solution: Contact distributor or seller or, failing that, our TSS for battery replacement.

When connecting UPS to mains, display does not illuminate

Possible cause: No voltage at input.

Solution: Check for mains voltage.

 

Possible cause: Input power cables badly connected.

Solution: Check input power cables firmly connected to mains and UPS.

 

Possible cause: Input cable connected to IEC output connector on UPS.

Solution: Correctly connect input cable to respective IEC connector.

Mains normal but UPS does not work in line mode

Causa posible: No hay tensión a la entrada.

Solución: Comprobar que los cables de alimentación de entrada se encuentren firmemente conectados a la red y al SAI.

 

Causa posible: Se disparó la protección de entrada.

Solución: Desenchufe el cable de alimentación del SAI y luego rearme la protección.

No output voltage

Possible cause: Input protection tripped by overload at output.

Solution: Disconnect load and reset input protection.

 

Possible cause: Battery discharged.

Solution: Charge batteries for at least 7 hours. If problem persists, contact distributor or seller or, failing that, our TSS.

 

Possible cause: UPS faulty.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: A56

Possible cause: Battery voltage too low.

Solution: Check input connection. Disconnect loads in battery mode.

Code: A57

Possible cause: Battery capacity too low.

Solution: Check input connection. Disconnect loads in battery mode.

Code: A59

Possible cause: Battery disconnected.

Solution: Stop UPS and connect its batteries.

Code: A64

Possible cause: Overload at output.

Solution: Disconnect excess loads from output sockets.

Code: A66

Possible cause: EPO (emergency power off) function activated.

Solution: Close EPO signal circuit (fit connector with jumper) to deactivate it.

Code: A68

Possible cause: UPS temperature very high.

Solution: Disconnect non-essential loads. Check fans working correctly and air inlets and outlets not blocked.

Code: A86

Possible cause: Inverter output voltage low.

Solution: Check AC input connection. Disconnect excess loads from output sockets.

Code: E12

Possible cause: Battery voltage low.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: E14

Possible cause: Overload at output.

Solution: Disconnect non-essential loads.

Code: E15

Possible cause: Loads unbalanced.

Solution: Turn off UPS. Check device’s loads.

Code: E18

Possible cause: Fan fault.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: E19

Possible cause: Overtemperature.

Solution: Turn off UPS. Turn on again and check fans working correctly and air inlets and outlets not blocked.

Code: E6

Possible cause: Inverter soft start fault.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: E7

Possible cause: Inverter output voltage too high.

Solution: Turn off UPS. Disconnect non-essential loads and restart.

Code: E8

Possible cause: Inverter output voltage too high.

Solution: Turn off UPS. Disconnect non-essential loads and restart.

Code: E9

Possible cause: Short circuit at output.

Solution: Turn off UPS. Loads and wiring may have problems, check both.

Barcelona Web Design: MontawebMONTAWEB.com
Welcome to Salicru. Select country/language
Algeria   Français
Angola   Português
Bahrain   English
Congo   Français
Côte d'Ivoire   Français
Egypt   English
Equatorial Guinea   Español   Português   Français
Iraq   English
Jordan   English
Kenya   English
Kuwait   English
Lebanon   English
Libya   English
Madagascar   Français
Mali   Français
Mauritania   Français
Morocco   Français
Niger   Français
Nigeria   English
Oman   English
Qatar   English
Reunion   Français
Saudi Arabia   English
Senegal   Français
South Africa   English
Syria   English
Tanzania   Français
Tunisia   Français   English
Turkey   English
Uganda   English
United Arab Emirates   English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it, adapt the content to your tastes and personalise our advertising, marketing and social media posts. Click on the corresponding buttons to accept all of them, reject them or configure your settings. Please see our Cookie Policy for more information.