SPS ADVANCE RT2 (Type G)
Line-interactive sine-wave tower/rack UPS 800 VA to 3000 VA
Effective protection for entry-level servers and IT equipment
Battery backup time much shorter than expected.

Possible cause: Batteries not fully charged.

Solution: Charge batteries for at least 8 hours and then check their charge level. If problem persists, contact distributor or seller or, failing that, our TSS.

 

Possible cause: Batteries defective.

Solution: Contact distributor or seller or, failing that, our TSS for battery replacement.

When connecting UPS to mains, display does not illuminate nor show any indications

Possible cause: No voltage at input.

Solution: Check for mains voltage.

 

Possible cause: Input power cables badly connected.

Solution: Check input power cables firmly connected to mains and UPS.

 

Possible cause: Input cable connected to IEC output connector on UPS.

Solution: Correctly connect input cable to respective IEC connector.

Code: 14

Possible cause: UPS turns off automatically due to short circuit at output.

Solution: Check output wiring and that connected loads not short-circuited.

Code: 27

Possible cause: Voltage of batteries too high or charger faulty.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: 28

Possible cause: Voltage of batteries too low or charger faulty.

Solution: Contact distributor or seller or, failing that, our TSS.

Code: 43

Possible cause: The UPS turns off automatically due to overload at output.

Solution: Disconnect the excess loads from the output sockets and restart it.

Code: 45

Possible cause: Charger does not provide output and battery voltage less than 10 V per element.

Solution: Disconnect excess load from output sockets and restart device.

Code: EP

Possible cause: EPO (emergency power off) function activated.

Solution: Close EPO signal circuit (fit connector with jumper) to deactivate it.

Code: NC

Possible cause: Internal or external batteries badly connected.

Solution: Check all batteries properly connected.

Code: OL

Possible cause: UPS overloaded.

Solution: Disconnect excess load from UPS output sockets.

 

Possible cause: The UPS is overloaded and connected loads are powered directly from the mains through the Bypass.

Solution: Disconnect excess load from UPS output sockets.

 

Possible cause: After repetitive overloads, the UPS is locked in Bypass mode and connected loads are powered directly from the mains through the Bypass.

Solution: Disconnect the excess loads from the output sockets, shut down the device and restart it.

Code: SF

Possible cause: Neutral to earth fault detection. Phase and neutral input cables inverted.

Solution: Disconnect input plug from AC power socket and invert connection of phase and supply neutral (rotate plug 180º).

Codes: 01, 02, 03, 11, 12, 13 und 41

Possible cause: Internal fault in UPS.

Solution: Contact distributor or seller or, failing that, our TSS.

Barcelona Web Design: MontawebMONTAWEB.com
Welcome to Salicru. Select country/language
Andorra   Català   Español
Armenia   English
Austria   Deutsch   English
Belarus   English
Belgium   Français   English
Bulgaria   English
Croatia   English
Cyprus   English
Czech Republic   English
Denmark   English
Estonia   English
Finland   English
France   Français
Georgia   English
Germany   Deutsch   English
Greece   English
Hungary   English
Ireland   English
Italy   English
Latvia   English
Lithuania   English
Luxembourg   Français   Deutsch
Malta   English
Netherlands   English
Norway   English
Poland   English
Portugal   Português
Romania   English
Russia   English
Serbia   English
Slovakia   English
Spain   Español   Català
Sweden   English
Switzerland   Français   Deutsch   English
Ukraine   English
United Kingdom   English
extralarge
large
tablet
mobile
We use proprietary and third-party cookies to keep track of how our website is used and to be able to improve it, adapt the content to your tastes and personalise our advertising, marketing and social media posts. Click on the corresponding buttons to accept all of them, reject them or configure your settings. Please see our Cookie Policy for more information.